{"id":3022,"date":"2021-12-13T13:48:06","date_gmt":"2021-12-13T05:48:06","guid":{"rendered":"https:\/\/www.hginstrument.com\/?p=3022"},"modified":"2021-12-13T13:48:06","modified_gmt":"2021-12-13T05:48:06","slug":"analysis-of-vortex-flowmeter-failure-cases","status":"publish","type":"post","link":"https:\/\/www.hginstrument.com\/pt\/analysis-of-vortex-flowmeter-failure-cases\/","title":{"rendered":"Analysis of vortex flowmeter failure cases"},"content":{"rendered":"

1. The vortex flowmeter suddenly has no current output.<\/strong>
\n[Fault check]: Check if the power supply is normal. Use handheld operator to test the loop, set the range of 0%, 25%, 50%, and 100% in the J10 parameter, and there is no current output. It is judged that the amplifier is faulty.
\n[Troubleshooting]: After replacing the amplifier and resetting the parameters (key parameters such as K factor, size, range, etc.), the vortex flowmeter returns to normal.<\/p>\n

2. The process has no flow, while the vortex flowmeter still shows flow.<\/strong>
\n[Fault check]: Firstly, check the setting of small signal removal, and finally, it is found that the parameter setting is wrong, and the size of the flowmeter is set incorrectly.
\n[Troubleshooting]: After modifying the meter size, the flowmeter displays normally. If the parameter setting is correct, it can be corrected by the low-pass filter capacitor.<\/p>\n

3. The vortex flowmeter shows a large error.<\/strong>
\n[Fault Check]: According to the technical agreement, it is found that the filter capacitor setting has a large deviation from the medium density.
\n[Troubleshooting]: According to the manual, after re-modifying the filter capacitor, the flowmeter displays normally. The filter capacitor is modified one level lower than density for liquid, and two levels lower than density for gas.<\/p>\n

4. The vortex flowmeter shows zero.<\/strong>
\n[Failure check]: For separate type vortex flowmeter, the coaxial cable is broken.
\n[Troubleshooting]: After replacing the coaxial cable, the meter displays normal.<\/p>","protected":false},"excerpt":{"rendered":"

Analysis of vortex flowmeter failure cases<\/p>","protected":false},"author":1,"featured_media":2768,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":[],"categories":[2130],"tags":[],"acf":[],"_links":{"self":[{"href":"https:\/\/www.hginstrument.com\/pt\/wp-json\/wp\/v2\/posts\/3022"}],"collection":[{"href":"https:\/\/www.hginstrument.com\/pt\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.hginstrument.com\/pt\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.hginstrument.com\/pt\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.hginstrument.com\/pt\/wp-json\/wp\/v2\/comments?post=3022"}],"version-history":[{"count":0,"href":"https:\/\/www.hginstrument.com\/pt\/wp-json\/wp\/v2\/posts\/3022\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.hginstrument.com\/pt\/wp-json\/wp\/v2\/media\/2768"}],"wp:attachment":[{"href":"https:\/\/www.hginstrument.com\/pt\/wp-json\/wp\/v2\/media?parent=3022"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.hginstrument.com\/pt\/wp-json\/wp\/v2\/categories?post=3022"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.hginstrument.com\/pt\/wp-json\/wp\/v2\/tags?post=3022"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}